NPSH Explained: NPSHa vs NPSHr and How to Calculate Both

At a glance: NPSH in 60 seconds

What NPSH is
Net Positive Suction Head: how much pressure the liquid has above its vapour pressure as it enters the pump. It is expressed in metres of column of the pumped liquid.
NPSHa (available)
What the installation delivers. It depends on the pressure above the tank, the suction lift, the friction losses, and the temperature and density of the fluid. It is calculated by the system designer.
NPSHr (required)
What the pump needs to avoid cavitation. It is determined by the manufacturer through testing, shown on the pump curve and rises with flow.
Design rule
NPSHa > NPSHr with a margin, across the whole flow range and at the lowest expected liquid level.
Formula
NPSHa = absolute pressure on the liquid − vapour pressure (both in metres of column) ± static height − suction friction losses.
Most often overlooked
Density: with 98 % sulphuric acid, the atmosphere only provides about 5.6 m of column, compared with 10.35 m for water.
Most favourable configuration
Pumps with the impeller submerged in the liquid, such as vertical sump pumps: with no suction lift, NPSHa is at its maximum.

Few abbreviations appear as often on a pump data sheet — and are as poorly understood — as NPSH. Almost everyone knows it has something to do with cavitation; far fewer know how to calculate it, and fewer still take into account that the same tank, with the same pipework, delivers a very different NPSH depending on the liquid it holds.

NPSH is really a simple balance sheet: how much pressure the liquid has to spare, above its vapour pressure, when it reaches the impeller. If that reserve is smaller than what the pump needs, the liquid boils inside the pump and cavitation sets in, with all the damage we describe in our guide What Is Pump Cavitation? Causes, Warning Signs and How to Prevent It.

In this article we explain exactly what NPSH available (NPSHa) and NPSH required (NPSHr) are, how to carry out an NPSH calculation step by step, what role suction lift, altitude, temperature and density play, and how to use the result to decide on the pump configuration. With worked examples and a focus on pumping corrosive fluids, where NPSH mistakes are particularly costly.

What NPSH is and why it decides whether a pump cavitates

What NPSH means: definition and units

NPSH stands for Net Positive Suction Head. It measures the energy per unit weight of the liquid at the pump suction flange — pressure plus velocity — minus the vapour pressure of the liquid itself at the operating temperature.

The key word is ‘net’. It is not enough to know the pressure at the suction: you need to know how much pressure there is above the boiling point. A liquid at 20 °C and another at 80 °C can reach the pump at the same pressure, yet the second will have far less NPSH, because it boils much more easily.

NPSH is expressed in metres of column of the pumped liquid, not in bar or in metres of water column. That choice of units is not arbitrary: in a centrifugal pump, the pressure needed to avoid cavitation behaves like a head. That is why manufacturers give NPSHr in metres, and why NPSHa must be calculated in metres of column of the actual fluid, with its actual density. As a reference, 1 bar is equivalent to about 10.2 m of water column, but only 5.5 m of concentrated sulphuric acid.

NPSH available (NPSHa): what the installation delivers

NPSHa is a property of the system, not of the pump. It sums up in a single figure everything that happens between the liquid surface and the suction flange:

  • The pressure on the liquid surface: atmospheric pressure in an open tank, which falls with altitude, or the internal pressure in a closed vessel, which may be below atmospheric if it operates under vacuum.

  • The static height: it adds to NPSHa if the liquid is above the pump (flooded suction) and subtracts from it if the pump has to lift the liquid (suction lift).

  • The friction losses in the suction line: straight runs, bends, valves, strainers and the pipe entrance.

  • The vapour pressure of the liquid, which depends on its nature and, above all, on its temperature.

Because it depends on the installation, NPSHa is not a fixed value: it falls as the tank empties, as the strainer clogs, as the process heats up or as the flow increases, because friction losses rise with the square of the velocity. That is why it must be calculated under the worst expected conditions, not the rated ones.

NPSH required (NPSHr): what the pump needs

NPSHr is a property of the pump. It depends on the design of the impeller eye, the inlet geometry of the vanes and the rotational speed, and it is determined by the manufacturer through testing. The usual procedure, set out in standards such as ISO 9906 (published in the UK as BS EN ISO 9906), is to reduce the NPSH at the suction at constant flow until the pump head drops by 3 %: that value is called NPSH3 and is the basis of NPSHr curves. Since the 2024 revision of the ANSI/HI 9.6.1 guideline, the Hydraulic Institute requires the NPSHr declared by the manufacturer to be equal to or greater than the tested NPSH3.

There are two important practical consequences. First, at the NPSH3 point the pump is already cavitating, so matching NPSHa to NPSHr is not enough; a margin is needed. Second, NPSHr is not constant. It rises with flow — gently at first and very steeply to the right of the best efficiency point — and it rises with rotational speed, roughly with its square. A pump with plenty of margin at 1,450 rpm can be very tight at 2,900 rpm.

AspectNPSH available (NPSHa)NPSH required (NPSHr)
A property of…The installation and the fluidThe pump
Who determines itThe system designer or process engineer, by calculation or measurementThe manufacturer, by testing (ISO 9906)
How it varies with flowFalls (friction losses increase)Rises, especially at high flows
What makes it worseSuction lift, altitude, temperature, density, clogged strainers, low tank levelHigher speed, flow away from the design point, worn impeller
How to improve itLowering the pump, enlarging the suction line, cooling, pressurisingReducing speed, running close to the BEP, choosing another size or model

How to calculate NPSH available step by step

The NPSHa formula and what each term means

On the installation side, the NPSH calculation comes down to a single expression, with every term in metres of column of the pumped liquid:

NPSHa = Pa / (ρ · g) ± Hz − Hf − Pv / (ρ · g)

  • Pa: absolute pressure on the free surface of the liquid, in Pa. In an open tank, it is the local atmospheric pressure.

  • ρ: density of the liquid at the operating temperature, in kg/m³. g = 9.81 m/s².

  • Hz: height difference between the liquid surface (minimum level) and the pump centreline, in m. Positive if the liquid is above the pump; negative if the pump draws from below.

  • Hf: total friction losses in the suction line at the maximum expected flow, in m.

  • Pv: vapour pressure of the liquid at the maximum operating temperature, in Pa absolute.

The first term is the starting ‘capital’, and it depends on where the plant is located. Atmospheric pressure falls with altitude, and with it the NPSHa of any open tank:

Plant altitudeAtmospheric pressure (kPa)In metres of water columnLoss compared with sea level
0 m101.310.35 m—
250 m98.410.04 m0.31 m
500 m95.59.75 m0.60 m
750 m92.69.46 m0.89 m
1,000 m89.99.18 m1.17 m
1,500 m84.68.63 m1.72 m

These are standard atmosphere values; actual pressure varies by a few kPa with the weather, which is another reason not to design with a bare minimum margin. Vapour pressure, for its part, is taken from tables or from the product data sheet: for water it rises from 0.24 m at 20 °C to almost 5 m at 80 °C, as detailed in the table in our pump cavitation guide.

Suction lift, density and temperature: the three terms that weigh most

Suction lift is the term the designer controls most directly. Every metre the pump has to lift the liquid is one metre less of NPSHa. In theory, with cold water at sea level, a pump could not draw from more than 10.35 m below it even with no losses and no cavitation; in practice, once friction losses, vapour pressure and NPSHr are taken into account, the usable suction lift is just a few metres.

Density is the most frequently forgotten term when pumping chemicals. Since atmospheric pressure is the same for any liquid, the denser the liquid, the fewer metres of column it represents:

Liquid (20 °C, indicative values)Density (kg/m³)Atmospheric pressure at sea level, in m of liquid column
Water99810.35 m
Hydrochloric acid 33 %≈ 1,1608.90 m
Sodium hypochlorite (≈ 13 %)≈ 1,2008.61 m
Ferric chloride 40 %≈ 1,4207.27 m
Sodium hydroxide (caustic soda) 50 %≈ 1,5206.80 m
Phosphoric acid 75 %≈ 1,5806.54 m
Sulphuric acid 98 %≈ 1,8405.61 m

The conclusion is clear-cut: with concentrated sulphuric acid, an open tank provides almost half the NPSH it would with water. An installation that happily draws water from 3 m below the pump can run out of margin with exactly the same layout in a fertiliser plant handling sulphuric or phosphoric acid. The pump’s NPSHr, on the other hand, stays practically the same in metres of column, because it depends on the hydraulics, not on density.

Temperature acts through vapour pressure, which rises exponentially. In hot surface treatment baths or process solutions at 60–80 °C, vapour pressure alone can consume 2 to 5 m of NPSHa. With concentrated acids or products that give off gases, such as hydrochloric acid, you must use the vapour pressure of the actual product, not that of water: the figure is given in the safety data sheet or the supplier’s documentation.

A complete NPSH calculation example

Let us take a typical case: a horizontal process pump transferring a dilute acid solution (density 1,050 kg/m³) at 50 °C from an open tank, in a plant located 250 m above sea level. The pump centreline is 2.5 m above the minimum tank level and the suction friction losses at maximum flow are 1.2 m. The pump curve shows an NPSHr of 3.2 m at the duty point and 4.5 m at maximum flow.

StepTermCalculationResult
1Atmospheric pressure in m of column98,400 Pa / (1,050 × 9.81)+9.55 m
2Suction liftPump 2.5 m above the minimum level−2.50 m
3Suction friction lossesPipe, bends, valve and strainer at maximum flow−1.20 m
4Vapour pressure at 50 °C12,350 Pa / (1,050 × 9.81)−1.20 m
5NPSH availableSum of steps 1 to 44.65 m
6Margin at the duty point4.65 − 3.2+1.45 m (acceptable)
7Margin at maximum flow4.65 − 4.5+0.15 m (insufficient)

The result illustrates a typical mistake: the pump meets the requirement at the rated point but runs out of margin at maximum flow, precisely when friction losses are highest and NPSHr is at its peak. If the same duty is handled by a vertical pump whose impeller runs half a metre below the minimum level, NPSHa rises to about 8.7 m: the suction lift and almost all the friction losses disappear.

In an existing installation, NPSHa can also be measured. Fit a compound gauge on the suction flange and suppose it reads −0.35 bar with water at 20 °C, in a plant at 250 m and with a velocity of 2 m/s at the flange. The absolute pressure is 98.4 − 35 = 63.4 kPa, i.e. 6.47 m of column; add the velocity head (v²/2g = 0.20 m) and subtract the vapour pressure (0.24 m): measured NPSHa = 6.43 m. If the gauge is not at the height of the pump centreline, that difference in elevation must also be corrected.

How to use NPSH to select and install the pump

NPSH margin, maximum suction lift and choosing the configuration

With NPSHa calculated under the worst conditions and NPSHr read from the curve at maximum flow, the check is straightforward: NPSHa must exceed NPSHr with a margin. As a practical guide, at least 0.5–1 m and, in relative terms, 10–30 % or more; the ANSI/HI 9.6.1 guideline refines those margins by type of application. With corrosive, hot or volatile fluids, it is advisable to stay at the upper end.

Rearranged, the same formula answers the question every designer asks: how high above the liquid level can I install the pump?

Hz max = Pa / (ρ · g) − Hf − Pv / (ρ · g) − NPSHr − margin

With water at 20 °C at sea level, 1 m of friction losses, an NPSHr of 3 m and a 1 m margin, the maximum suction lift is about 5.1 m. With 98 % sulphuric acid and the same data, it drops to about 0.6 m: in practice, the pump must be installed with flooded suction or submerged.

This is why NPSH determines not only the size of the pump but also its configuration. Within the Tecnium Pumps range of plastic pumps:

  • When the liquid sits in a pit, a bund or a buried tank, BT series vertical sump pumps run with the casing submerged: with no suction lift, NPSHa is as high as it can be. They also have no mechanical seal and can run dry, which is very useful in neutralisation tanks or in waste water treatment, where the level varies.

  • To draw directly from storage tanks with the pump mounted outside, BV series vertical pumps and BHS series vertical motor pumps combine sealless designs with dry-running capability.

  • Where there is flooded suction and room for a horizontal pump, BN process pumps, built to ISO 2858 / EN 22858, offer wide hydraulic coverage to choose the size and speed whose NPSHr suits the installation; they can be fitted with a variable speed drive (VSD), which lowers NPSHr as the speed is reduced.

  • For toxic or volatile products, BKM series magnetic drive pumps eliminate leaks, but they call for a particularly well-verified NPSH, because their bushes are lubricated by the pumped liquid itself.

NPSH: frequently asked questions

What is NPSH in a pump?

It is the Net Positive Suction Head: the pressure the liquid has as it enters the pump above its vapour pressure, expressed in metres of liquid column. A distinction is made between NPSH available, which the installation delivers, and NPSH required, which the pump needs to avoid cavitation.

How do you calculate NPSH available?

Take the absolute pressure on the liquid expressed in metres of column, add or subtract the height difference between the liquid level and the pump, and subtract the suction friction losses and the vapour pressure of the liquid, also in metres. It must be calculated at the minimum level, the maximum temperature and the maximum flow.

Where do I find the NPSH required of a pump?

On the performance curve supplied by the manufacturer, usually in a graph below the head–flow curve. It is obtained by testing, normally as the NPSH at which the head drops by 3 % (NPSH3). It must be read at the maximum operating flow, not just at the rated point.

What is the maximum suction lift of a pump?

It depends on the installation and the liquid: it is the atmospheric pressure in metres of column minus the friction losses, the vapour pressure, the NPSHr and the safety margin. With cold water it is usually just a few metres; with dense or hot liquids it can be practically zero.

Why is NPSH expressed in metres rather than bar?

Because the pressure a centrifugal pump needs to avoid cavitation behaves like a head: in metres of column, NPSHr is practically independent of density. That is why NPSHa must be calculated in metres of column of the actual liquid, using its density at the operating temperature.

What happens if NPSHa is lower than NPSHr?

The pump cavitates: the liquid vaporises at the impeller inlet, head and flow fall, and the collapsing bubbles erode the impeller and damage the seal and bearings. The solution is to increase the NPSH available, reduce the NPSH required or switch to a configuration with the impeller submerged.

Do you need to check the NPSH of a new or existing installation? Send our technical team the fluid, its concentration and maximum temperature, the required flow and head, the plant altitude, the minimum liquid level relative to the pump and a sketch of the suction pipework. We will calculate the NPSH available, compare it with the NPSH required by the right pump and propose the safest configuration. Request your free quote.